SURVSNA OH 02 ILLUMINATION
Report NumberOH-2026-123-R0
Page NumberPage 1 of 32
RevisionsRevision 0
Survey Date02 Sept 2026
SafeNet Africa

Occupational Hygiene Monitoring Survey Report

Illumination Survey Report

ABC Manufacturing · Cape Town Plant

02 Sept 2026

Project Number OH-2026-123 · Revision 0

Survey Information Details

Report NumberOH-2026-123-R0
Project NumberOH-2026-123
ClientABC Manufacturing
Site / PremisesCape Town Plant
Physical Address14 Marconi Rd, Montague Gardens, Cape Town
Survey Date02 Sept 2026
Stress FactorIllumination
SurveyorNomsa Dlamini
Technical SignatoryRiaan de Villiers
Applicable LegislationEnvironmental Regulations For Workplaces, 1987 · SANS 10114-1
Occupational Exposure LimitMinimum Maintained Illuminance Per Task As Per SANS 10114-1

1.0 Executive Summary

ABC Manufacturing contracted The Safety Network (Africa) (Pty) Ltd to conduct a illumination survey at Cape Town Plant, 14 Marconi Rd, Montague Gardens, Cape Town. The survey was conducted on 02 Sept 2026 by Nomsa Dlamini.

Two of the four positions measured below the minimum maintained illuminance required for the task performed.

2.0 Purpose Of The Survey

  1. Measure illuminance levels at defined task and walkway positions
  2. Compare measured levels with the minimum values prescribed by legislation
  3. Identify positions where lighting is insufficient for the task performed
  4. Recommend corrective lighting measures

3.0 Contents Of Report

  1. 1.0Executive Summary
  2. 2.0Table Of Contents
  3. 3.0List Of Tables, Figures And Diagrams
  4. 4.0List Of Terms And Abbreviations
  5. 5.0Introduction
  6. 6.0Monitoring Methods And Procedure Followed
  7. 7.0Results And Discussion
  8. 8.0Recommendations
  9. 9.0Conclusion
  10. 10.0Indemnity And Signatures
  11. 11.0References
  12. 12.0Annexures To The Report

4.0 Instruments Used

InstrumentSerial NumberCalibration Due
Gilian 5000 pumpGIL-440204 Nov 2026
Gilian 5000 pumpGIL-440722 Oct 2026
SKC Airchek TOUCHSKC-221027 Sept 2026

5.0 Results And Discussion

PositionAreaTaskMeasured LuxRequired LuxCompliant
I-01Production HallMachine Operation410300Yes
I-02Quality BenchFine Inspection480750No
I-03Store AisleWalkway128100Yes
I-04Workshop BenchFitting296500No

Two of the four positions measured below the minimum maintained illuminance required for the task performed.

6.0 Recommendations

  1. Install task lighting at the quality inspection bench
  2. Replace degraded luminaires above the workshop bench
  3. Introduce a scheduled luminaire cleaning and replacement programme
  4. Re-survey illumination within 24 months

7.0 Conclusion

Lighting is generally adequate. Task lighting upgrades are required at two positions.

8.0 Annexures To The Report

  • Annexure A — Certificate Of Approval As A Department Of Employment And Labour Approved Inspection Authority
  • Annexure B — SAIOH Certificates Of Surveyor And Technical Signatory
  • Annexure C — Equipment Calibration Certificates
  • Annexure D — Raw Measurement Data
  • Annexure E — Photo Log
  • Annexure F — Site And Floor Plans

The Safety Network (Africa) (Pty) Ltd

T/A SafeNet Africa

Dept. of Employment and Labour: AIA OH 0242 CI062

Signature of Technical Signatory

Riaan de Villiers

Signature of Surveyor

Nomsa Dlamini